Clack control valve error code 101
Jan 31, 2024, 13:54:51
E1, Err – 1001, Err – 101 appear in the display
What does error code 101 mean?
The controller cannot detect the motor movement.
ATTENTION: Risk of injury! Only carry out the following work as a specialist. If the gear suddenly starts running again, there is an acute risk of injury. If in doubt, please do not hesitate to contact us first.
Possible causes:
The motor is not plugged in properly and the gears do not fit / motor cable is damaged or not connected
Disconnect the power, make sure the motor is fully engaged, check if the cables are broken. Make sure the motor's two-pin connector is connected to the two-pin connector on the circuit board with the "MOTOR" connector. Press the NEXT and REGEN buttons for 3 seconds to resynchronize the software with the piston position, or disconnect the power from the PC board for 5 seconds and then reconnect it.
The circuit board is not properly locked into the holder
Insert the board into the holder properly and then press the NEXT and REGEN buttons for 3 seconds to re-synchronize the software with the piston position or disconnect the power from the PC board for 5 seconds and then reconnect it.
Reduction gears are missing
Replace the missing gears.
You may also be interested in
ManualsConnection & Setting
possible error causes
Advice & offers
Order & Payment